Re: Homing Problem on Triac

Post by Denford Admin »

I have attached a copy of the wiring diagram
Hi,
That .tif file wouldn't show through the Forum - I don't know how it was created but I'd recommend exporting or saving images to .JPG and keep them at about 1024x768 pixels. If you want more higher detail then .pdf is the way to go.
I've created a .jpg of your drawing which is only 70 Kb whereas the .tif was 2000 Kb (which makes a big difference to our limited server space)
CNC Guru
CNC Guru
Posts: 1929
Joined: Fri 24 Feb , 2006 17:09 pm
Location: Brighouse
CNC Guru
CNC Guru
Re: Homing Problem on Triac

Post by Martin »

You may have a short inside the lube pump. Remove the lid from the pump & check the motor coil & that no wires are shorting to ground.
Posts: 9
Joined: Sat 05 Nov , 2011 22:17 pm
Hardware/Software: Denford Triac PC
QuickCAM 3D
VR Milling 2.25.3.917
Re: Homing Problem on Triac

Post by benners »

I have had the lube pump housing apart and can see nothing that looks out of the ordinary. I have disconnected the pump motor from the cover and again tried to M3 but the same thing occurs. Just thinking out loud - is that to be expected as there is nothing connected to the wires or is the issue with the motor and not something in between the motor and rack. Is the assumption that this expected behaviour correct?
Site Admin
Posts: 3651
Joined: Fri 10 Feb , 2006 12:40 pm
Hardware/Software: Go to User Control Panel > Profile
Enter as much information about your CNC hardware and software as you can - it makes it easier for everyone to know what you're talking about then.
Location: Sunny Brighouse
Contact:
User avatar
Site Admin
Re: Homing Problem on Triac

Post by Denford Admin »

I have disconnected the pump motor from the cover and again tried to M3 but the same thing occurs
If the motor has been disconnected and you still get a short/current drain then it could be a problem in the connector or a wire that's lost it's insulation.
Quickest way to prove that would be put a new wire from the SGR contact directly to the motor
CNC Guru
CNC Guru
Posts: 1929
Joined: Fri 24 Feb , 2006 17:09 pm
Location: Brighouse
CNC Guru
CNC Guru
Re: Homing Problem on Triac

Post by Martin »

It may also be worth belling out the wire. Just to make sure it is the same wire.